Chapter 7 Maintenance and Troubleshooting
Group F8: Operation Panel and Display
F8.01
MK Key function selection
MK key refers to multifunctional key. You can set the function of the MK key by using this parameter.
You can perform switchover by using this key both in stop or running state.
0: MK key disabled
This key is disabled.
1: Switchover between operation panel control and remote command control
You can perform switchover from the current command source to the operation panel control (local
operation). If the current command source is operation panel control, this key is invalid.
2: Switchover between forward rotation and reverse rotation
You can change the direction of the frequency reference by using the MK key. It is valid only when the
current command source is operation panel control.
3: Forward JOG
You can perform forward JOG (FJOG) by using the MK key.
4: Reverse JOG
You can perform reverse JOG (FJOG) by using the MK key.
F8.02
STOP/RESET key function
0: STOP/RESET key enabled only in operation panel control
1: STOP/RESET key enabled in any operation mode
F8.03
LED display running parameters 1
A maximum of 32 parameters in the running status can be viewed in F8.03 and F8.04. The display
starts from the lowest bit of F8.03. A total of 13 parameters in the stop can be viewed in F8.05.
Bit07
Bit06
X input
Bus
status
voltage
Bit15
Bit14
PID
PID
feedback
setting
LED display running
F8.04
parameters 2
Bit07
Bit06
Linear
Length
speed
value
Bit15
Bit14
Communi
cation
Reserved
setting
value
F8.05
LED display stop parameters
Bit07
Bit06
Count
AI3
value
voltage
Bit15
Bit14
Bit05
Bit04
Output
Output
torque
power
Bit13
Bit12
Pulse
AI3
setting
voltage
frequency
Bit05
Bit04
Count
feedback
value
speed
Bit13
Bit12
Remaining
PLC
running
stage
time
Bit05
Bit04
AI2
AI1
voltage
voltage
Bit13
Bit12
Pulse
setting
frequency
Range:0~4
Range:0~1
Range:0x0000~0xFFFF
Bit03
Bit02
Output
Output
voltage
current
Bit11
Bit10
AI2
AI1
voltage
voltage
Range:0x0000~0xFFFF
Bit03
Bit02
Auxiliary
Main
frequency
frequency
display
display
Bit11
Bit10
Output
Overload
current
count
percentage
Range:0x0000~0xFFFF
Bit03
Bit02
Digital output
X input
status
status
Bit11
Bit10
PID setting
Load
speed
- 104 -
JT550 Series Inverter Manual
Default:0
Default:1
Default:0x001F
Bit01
Bit00
Set
Running
frequency
frequency
Bit09
Bit08
DO output
Reserved
status
Default:0x0000
Bit01
Bit00
Load
PID
speed
output
display
Bit09
Bit08
Current
Current
running
power-o
time
n time
Default:0x0033
Bit01
Bit00
Bus
Set
voltage
frequency
Bit09
Bit08
PLC
Length
stage
value