JT550 Series Inverter Manual
Frequency level detection
25
FDT2 output
26
Frequency 1 reached
27
Frequency 2 reached
28
Current 1 reached
29
Current 2 reached
30
Timing reached
31
AI1 input limit exceeded
32
Load becoming 0
33
Reverse running
34
Zero current state
Module temperature
35
reached
Software current limit
36
exceeded
Frequency lower limit
37
reached
38
Alarm output
Current running time
40
reached
41
Analog levels:ADT1
42
Analog levels:ADT2
44
The X1 state
45
The X2 state
F3.06
F3.07
F3.08
DO terminal output pulse frequency range of 0.01kHz ~ F3.09 (DO maximum output frequency),
F3.09 can be set between 0.01kHz ~ 100.00kHz.
Analog output AO1 and AO2 output range of 0V ~ 10V, or 0mA ~ 20mA.
Value
0
Running frequency
1
Set frequency
2
Output current
3
Output torque
4
Output power
5
Output voltage
6
Pulse input
7
AI1
8
AI2
9
AI3
10
Length
11
Count value
12
Communication setting
13
Motor rotational speed
14
Output current
15
Output voltage
Refer to the descriptions of F4.28 and F4.29
Refer to the descriptions of F4.30 and F4.31
Refer to the descriptions of F4.32 and F4.33
Refer to the descriptions of F4.38 and F4.39
Refer to the descriptions of F4.40 and F4.41
If the timing function (F4.42) is valid, the terminal becomes ON
after the current running time of the inverter reaches the set time.
If AI1 input is larger than the value of F4.46 (AI1 input voltage
upper limit) or lower than the value of F4.45 (AI1 input voltage
lower limit), the terminal becomes ON.
If the load becomes 0, the terminal becomes ON.
If the inverter is in the reverse running state, the terminal becomes
ON.
Refer to the descriptions of F4.34 ,F4.35
If the heatsink temperature of the inverter module (F8.07)reaches the
set module temperature threshold (F4.47), the terminal becomes ON
Refer to the descriptions of F4.36,F4.37
If the running frequency reaches the lower limit, the terminal
becomes ON. In the stop state, the signal is still ON
If a fault occurs on the inverter and the inverter continues to run, the
terminal outputs the alarm signal.
If the current running time of inverter exceeds the value of F4.53, the
terminal becomes ON.
Output OFF when the analog input voltage is higher than F4.57, the
output is ON, less than F4.56
When the analog input voltage is higher than F4.59, output ON, OFF
output below the F4.58
The X1 current state
The X2 current state
Table 7-4 Functions of output terminals
DO output function selection
AO1output function selection
AO2output function selection
Function
0 to maximum output frequency
0 to maximum output frequency
0 to 2 times of rated motor current
0 to 2 times of rated motor torque
0 to 2 times of rated power
0 to 1.2 times of rated inverter voltage
0.01kHz~100.00kHz
0V~10V
0V~10V(0~20mA)
0V~10V
0 to maximum set length
0 to maximum count value
0.0%~100.0%
0 to rotational speed corresponding to output max.freq
0.0A~1000.0A
0.0V~1000.0V
Range:0~16
Range:0~16
Range:0~16
Range
- 89 -
Chapter 7 Maintenance and Troubleshooting