JT550 Series Inverter Manual
Asynchronous machine standstill since the previous identification, you must set the correct motor type
and motor nameplate parameters F1.00 ~ F1.05. Stationary self-identification, the drive can get F1.06 ~
F1.08 three parameters.
Action Description: Set the function code is 1, then press the RUN key, the drive will still self-identify.
2: complete self-identification
To ensure the dynamic control performance of the inverter, please choose the complete
self-identification, and the motor must be separated from the load to keep the motor for the no-load condition.
Complete self-identification process, the inverter will be stationary self identification, and then follow the
acceleration time to accelerate to 80% F0.17 rated motor frequency, after a period of time, according to the
deceleration time F0.18 deceleration stop and end self identification.
Asynchronous machine complete self-identification, the drive can get F1.06 ~ F1.10 five motor
parameters, and the encoder AB phase sequence F1.30, vector control current loop PI parameters F5.13 ~
F5.16.
Action Description: Set the function code is 2, then press the RUN key, the drive will be a complete
self-identification.
Group F2:Input Terminal
JT550 series inverter have five multi-function input terminals X1 ~ X5 (X5 which can be used as
high-speed pulse input), two analog input terminal AI1, AI2 (which can be used as a voltage input AI2, but
also as a current input), a keyboard potentiometer.
F2.00
F2.01
F2.02
F2.03
F2.04
F2.05
F2.06
F2.07
F2.08
F2.09
Input Terminal Setting list:
value
0
No function
1
Forward RUN (FWD)
2
Reverse RUN (REV)
3
Three-line control
4
Forward JOG (FJOG)
5
Reverse JOG (RJOG)
6
Terminal UP
7
Terminal DOWN
8
Coast to stop
X1 function selection
X2 function selection
X3 function selection
X4 function selection
X5 function selection
X6 function selection
X7 function selection
X8 function selection
X9 function selection
X10 function selection
Function
The terminal is used to control forward or reverse RUN of the
inverter.
The terminal determines three-line control of the inverter. For
details, see the description of F2.11.
FJOG indicates forward JOG running, while RJOG indicates
reverse JOG running. The JOG frequency,acceleration time and
deceleration time are described respectively in
F4.00,F4.01,F4.02.
If the frequency is determined by external terminals, the
terminals with the two functions are used as increment and
decrement commands for frequency modification.When the
frequency source is digital setting, they are used to adjust the
frequency.
The inverter blocks its output, the motor coasts to rest and is
not controlled by the inverter.
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Range:0~50
Description
- 81 -
Chapter 7 Maintenance and Troubleshooting
Default:1
Default:4
Default:9
Default:12
Default:13
Default:0
Default:0
Default:0
Default:0
Default:0