Veichi JT550 Series Manual page 28

Table of Contents

Advertisement

Chapter 3 Electrical Installation
Figure 3.11 Three -Phase 110-132kW Inverter's Terminal Layout of Major Circuit and Size Diagram
Model
JT550-T3-110G/132P
JT550-T3-132G/160P
Figure 3.12 Three -Phase 160-200kW Inverter's Terminal Layout of Major Circuit and Size Diagram
Model
JT550-T3-160G/185P
JT550-T3-200G/220P
Figure 3.13 Three -Phase 220-280kW Inverter's Terminal Layout of Major Circuit and Size Diagram
Model
JT550-T3-220G/250P
JT550-T3-250G/280P
JT550-T3-280G/315P
Rated
Recommended
Input
Input Output
Current
Power Cable
A
mm²
214
120
256
150
Rated
Recommended
Input
Input Output
Current
Power Cable
A
mm²
307
185
385
2*120
Rated
Recommended
Input
Input Output
Current
Power Cable
A
mm²
430
2*120
468
2*120
525
2*150
Recommended
Solderless
Terminal
Models
DT120-10
DT150-10
68mm
42mm
Recommended
Recommended
Solderless
Terminal
Models
DT185-12
DT240-12
95mm
63mm
M16组合螺钉
Recommended
Solderless
Terminal
Models
DT240-16
DT240-16
DT300-16
- 28 -
JT550 Series Inverter Manual
Recommended
Recommended
Solderless
Ground Cable
Terminal
mm²
Models
70
RNB60-10
70
RNB60-10
M12 Combination Screw
M12组合螺钉
Recommended
Solderless
Ground Cable
Terminal
mm²
Models
95
RNB80-12
120
DT120-12
M16 Combination Screw
Recommended
Recommended
Solderless
Ground Cable
Terminal
mm²
Models
120
DT120-16
120
DT120-16
150
DT150-16