F2.33
AI curve selection
Hundred's digit(AI3curve
selection)
1:Curve 1:F2.16~F2.19
2:Curve 2:F2.20~F2.23
3:Curve 3:F2.24~F2.27
4:Curve 4:P0.00~P0.07
5:Curve 5:P0.08~P0.15
The unit's digit, ten's digit and hundred's digit of this parameter are respectively used to select the
corresponding curve of AI1, AI2 and AI3. Any of the five curves can be selected for AI1, AI2 and AI3.
Setting for AI less than minimum
F2.34
This parameter is used to determine the corresponding setting when the analog input voltage is less
than the minimum value. The unit's digit, ten's digit and hundred's digit of this parameter respectively
correspond to the setting for AI2, AI2 and AI3.
If the value of a certain digit is 0, when analog input voltage is less than the minimum input, the
corresponding setting of the minimum input (F2.17,F2.21,F2.25) is used.
If the value of a certain digit is 1, when analog input voltage is less than the minimum input, the
corresponding value of this analog input is 0.0%.
F2.35
X1 switch-on delay
F2.36
X1 switch-off delay
F2.37
X2 switch-on delay
F2.38
X2 switch-off delay
F2.39
X3 switch-on delay
F2.40
X3 switch-off delay
ON
OFF
actual
F2.41
Ten thousand's digit
X5
0: High level valid
The X terminal is valid when connected with COM, and invalid when disconnected from COM.
1: Low level valid
The X terminal is invalid when connected with COM, and invalid when disconnected from COM.
Group F3:Output Terminals
F3.00
Y2/DO terminal output mode
Y2 / DO terminal is re-programmable terminals, can be used as high-speed pulse output terminal (DO),
can be used as an open-collector digital output terminal (Y2).
0: Pulse output (FMP)
1: Switch signal output (FMR)
DO as a pulse output, the maximum frequency of the output pulse is 100kHz, DO-related functions,
see Note F3.06.
Ten's digit (AI2 curve selection)
1:Curve 1:F2.16~F2.19
2:Curve2:F2.20~F2.23
3:Curve3:F2.24~F2.27
4:Curve4:P0.00~P0.07
5:Curve5:P0.08~P0.15
input
Switch-on delay
X valid mode selection
Thousand's digit
X4
Range:000~555
Range:000~111
0.0s~3600.0s
0.0s~3600.0s
0.0s~3600.0s
0.0s~3600.0s
0.0s~3600.0s
0.0s~3600.0s
Switch-off delay
Range:00000~11111
Hundred's digit
X3
Range:0~1
- 87 -
Chapter 7 Maintenance and Troubleshooting
Default:321
Unit's digit (AI1 curve
selection)
1:Curve 1:F2.16~F2.19
2:Curve2:F2.20~F2.23
3:Curve3:F2.24~F2.27
4:Curve4:P0.00~P0.07
5:Curve5:P0.08~P0.15
Default:000
0.0s
0.0s
0.0s
0.0s
0.0s
0.0s
Default:00000
Ten's digit
Unit's digit
X2