Veichi JT550 Series Manual page 51

Table of Contents

Advertisement

JT550 Series Inverter Manual
Function
Parameter Name
Codes
F2.10
Terminal X Filter Time 0.000s~1.000s
Terminal Command
F2.11
Mode
Terminal UP/DOWN
F2.12
Rate of Change
F2.13
AI1 Filter Time
F2.14
AI2 Filter Time
F2.15
AI3 Filter Time
AI Curve 1 Minimum
F2.16
Input
Corresponding Setting
F2.17
of AI Curve 1
Minimum Input
AI Curve 1 Maximum
F2.18
Input
Corresponding Setting
F2.19
of AI Curve 1
Maximum Input
AI Curve 2 Minimum
F2.20
Input
Corresponding Setting
F2.21
of AI Curve 2
Minimum Input
AI Curve 2 Maximum
F2.22
Input
Corresponding Setting
F2.23
of AI Curve 2
Maximum Input
AI Curve 3 Minimum
F2.24
Input
Corresponding Setting
F2.25
of AI Curve 3
Minimum Input
AI Curve 3 Maximum
F2.26
Input
Corresponding Setting
F2.27
of AI Curve 3
Maximum Input
PULSE Minimum
F2.28
Input
Corresponding Setting
F2.29
of PULSE Minimum
Input
PULSE Maximum
F2.30
Input
Corresponding Setting
F2.31
of PULSE Maximum
Input
Range of Settings
0: Two-Wire Mode 1
1: Two-Wire Mode 2
2: Three-Wire Mode 1
3: Three-Wire Mode 2
0.01Hz/s~65.535 Hz/s
0.00s~10.00s
0.00s~10.00s
0.00s~10.00s
0.00V~F2.18
-100.0%~+100.0%
F2.16~+10.00V
-100.0%~+100.0%
0.00V~F2.22
-100.0%~+100.0%
F2.20~+10.00V
-100.0%~+100.0%
0.00V~F2.26
-100.0%~+100.0%
F2.24~+10.00V
-100.0%~+100.0%
0.00kHz~F2.30
-100.0%~100.0%
F2.28~100.00kHz
-100.0%~100.0%
- 51 -
Chapter 7 Maintenance and Troubleshooting
Default
0.010s
0
1.00Hz/s
0.10s
0.10s
0.10s
0.20V
0.0%
10.00V
100.0%
0.20V
0.0%
10.00V
100.0%
0.20V
0.0%
10.00V
100.0%
0.00kHz
0.0%
50.00kHz
100.0%
Property

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents