Bennett Horizon 2.1 Series Installation Manual
This manual contains installation instructions for installing the Horizon 2.1 Series dispenser. Included are mechanical,
transporting, wiring, and start-up instructions. Please refer to the original manufacturer's installation instructions for
proper installation for aboveground and underground liquid storage systems, shear valves, hoses, and breakaways.
Related Documents
Bennett 515 Pump Controller Installation & Service Manual ---------------------------------------------Part# 105022
Bennett 919 Electronics Technical Manual ----------------------------------------------------------------Part# 135444
Bennett Horizon 2.1 Parts Manual -------------------------------------------------------------------------Part# N/A
Horizon 2.1 Maintenance Schedule and Log --------------------------------------------------------------Part# N/A
Horizon 2.1 Series Audit Report --------------------------------------------------------------------------Part# N/A
Simply Secure Payment PCI 3.1 (SSP Large Display) Programming, Service, and Parts Manual --------Part# 128203
Power Requirements
AC Power Input, Electronic ..........................................................................................................120/240 VAC, 50/60 Hz. 350 Watts Max.
DC Power Supply Output ....................................................................................................................................... +12 VDC at 2.0 Amps Max.
Lead-Acid Battery Output ...................................................................................................................................... +12 VDC at 5.0 Amp Hours
Nickel-Cadmium Battery Output .............................................................................................................. +3.6 VDC at 250 Milliamp Hours
Environmental Requirements
Operating Temperature Range ............................................................................................................. -40°C to +65°C (-40°F to +150°F)
Humidity ............................................................................................................................................................................... 0-95% non-condensing
Dimensions
2000 Series Maximum ............................................................................................................... * 48" (width) x 20" (depth) x 94" (height)
2400-L Low Hose Maximum ................................................................................................... * 36" (width) x 20" (depth) x 60" (height)
2400-H High Hose Maximum ................................................................................................. * 36" (width) x 20" (depth) x 94" (height)
Horizon 2.1 Series Estimated Shipping Weight ............................................................................................500 pounds/227 kilograms
Codes and Standards
NFPA 30 – Flammable and Combustible Liquids Code
NFPA 30A – Code for Motor Fuel Dispensing Facilities and Repair Garages
NFPA 70 – National Electric Code®
ASME B31.3 – Process Piping
International Fire Code – 2000 Edition
Introduction
1
Introduction
+24 VDC at 2.0 Amps Max.
*without valance
*without valance
*without valance