Repair Procedures - Daikin RXTA30B2V1B Service Manual

R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

4
|
Components

4.22.2 Repair procedures

To remove the thermistor
Service manual
200
Does the measured resistance of the
thermistor match with the
temperature determined resistance?
Yes
No
Indoor unit air (room) thermistor
FTXTA-B UNITS
As the indoor unit air (room) thermistor is located on the humidity sensor PCB,
replace the humidity sensor assembly, see
FTXTM-R UNITS
As the indoor unit air (room) thermistor is located on the display PCB, remove the
display PCB as described in the steps below:
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove the display panel from the indoor unit.
2 Pull up the bottom of the indication lamp cover.
b
a Indication lamp cover
b Display PCB
3 Remove the display PCB from the back side of the indication lamp cover.
4 Disconnect the connector from the display PCB.
5 To install the indoor unit air (room) thermistor, see
4
procedures" [
 200].
FTXTP-M AND ATXTP-M UNITS
Action
Correct the wiring between the
thermistor connector on the PCB and
the intermediate connector, see
"7.2 Wiring
Replace the specific thermistor, see
"4.22.2 Repair
"4.7.2 Repair
"4.17 Plate
a
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
4
diagram" [
 232].
4
procedures" [
 200].
4
procedures" [
 87].
4
work" [
 144].
"4.22.2  Repair
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02