Plate Work; Outdoor Unit - Daikin RXTA30B2V1B Service Manual

R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

4
|
Components

4.17 Plate work

4.17.1 Outdoor unit

To remove the refrigerant connection cover
Service manual
144
7 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
8 Install the support plate. Install and tighten the 2 screws to fix the support
plate.
f g
a Heat exchanger thermistor
b Outdoor air thermistor
c Guard net
d Screw
e Support plate
f Heat exchanger pipe
g Heat exchanger pipe
9 Install the guard nets. Install and tighten the screws to fix the guard nets.
10 Install the heat exchanger thermistor and air thermistor in their holder.
11 Install the putty and insulation on the appropriate piping.
12 Perform a pressure test, see
13 Add
refrigerant
4
procedures" [
 216].
Is the problem solved?
Yes
No
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
b
a
c
d
"5.2.1 Checking
to
the
refrigerant
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
e
c
4
procedures" [
 211].
circuit,
see
"5.2.2  Repair
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
R32 Optimized Heating 4 Split