Daikin RXTA30B2V1B Service Manual page 175

R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
a
b
a Main swing flap
b Secondary swing flap
c Screw (swing flap motor fixation)
d Swing flap motor
5 Remove (pull back) the swing flap motor from the indoor unit.
6 Disconnect the wiring harness from the swing flap motor.
7 To install the swing flap motor, see
FTXTP-M and ATXTP-M units
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see
1 Remove the cover.
b
a Cover
b Screw
c Swing flap motor
2 Disconnect the connector from the swing flap motor.
3 Remove the screw from the swing flap motor.
4 Remove the swing flap motor from the swing flap.
5 To install the swing flap motor, see
c
d
"Repair
procedures" [
"4.17 Plate
c
a
"Repair
procedures" [
4
Components
|
4
 181].
4
work" [
 144].
4
 174].
Service manual
175