To set the snowfall prevention settings
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
In heavy snow areas, snow may cover the outdoor unit, a snowdrift pile may be
formed near the outdoor unit, or icicles may reach the outdoor unit during the
night. If such conditions are left uncorrected, operating the air conditioner in the
next morning can cause damage to the outdoor unit fan or result in fan lock error,
disallowing proper heating operation in some cases.
In this case the snowfall prevention setting can be used.
1 Cut the jumper J12 on the circuit board using nippers or a similar tool to start
the outdoor unit fan intermittently at low ambient.
7
Technical data
|
Service manual
261