Daikin RXTA30B2V1B Service Manual page 112

R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

4
|
Components
To check the fuse of the indoor unit main PCB
Service manual
112
3 Check that the wiring corresponds with the wiring diagram, see
4
diagram" [
 232].
INFORMATION
Correct the wiring as needed.
Is the problem solved?
Yes
No
Prerequisite: First perform all earlier checks of the indoor unit main PCB, see
"4.11.1 Checking
procedures" [
1 Measure the continuity of the fuse. If no continuity is measured, the fuse has
blown.
A
a
A Indoor unit FTXTA-B
a Fuse F1U
A
a
A Indoor unit FTXTM-R
a Fuse F1U
Action
No further actions required.
Return to
"4.10.1 Checking
procedures" [
power PCB and continue with the next
procedure.
4
 109].
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
"7.2  Wiring
4
 97] of the indoor unit
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents