R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Pins
15-14
15-13
15-12
15-11
14-13
14-12
14-11
13-12
13-11
12-11
Swing raster motor resistance
measurements are correct?
Yes
No
3 Remove the swing raster motor, see
4 Measure the resistance between the following pins of the connector on the
swing raster motor.
Result: The measurements MUST be as shown in the table below.
Pins
1-2
1-3
1-4
1-5
2-3
2-4
2-5
3-4
3-5
4-5
Swing raster motor resistance
measurements are correct?
Yes
No
4
Measured resistance (Ω)
353.4~406.6
706.8~813.2
Action
Return to the troubleshooting of the
specific error and continue with the
next procedure.
Continue with the next step.
"4.21.2 Repair
procedures" [
Measured resistance (Ω)
353.4~406.6
706.8~813.2
Action
Replace the swing raster motor wiring
harness, see
"4.21.2 Repair
procedures" [
4
 186].
Replace the swing raster motor, see
"4.21.2 Repair
procedures" [
Components
|
4
 186].
4
 186].
Service manual