To control the indoor unit fan during thermostat off in cooling
Service manual
258
FTXTP-M and ATXTP-M units
INFORMATION
When there is a big difference between the indoor room temperature and the set
temperature in heating mode, adjust the target set temperature field setting.
▪ Target temperature = remote controller set temperature + 2.5°C. For
example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1 Press
,
, and
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 7.
7 Press
to confirm.
8 Press
.
9 Select the value to set the desired target temperature:
▪ 0 = –2,0°C
▪ 1 = –1,0°C
▪ 2 = 0°C (factory setting)
▪ 3 = +1,0°C
▪ 4 = +2,0°C
10 Press
to confirm.
FTXTA-B and FTXTM-R units
1 Press
,
, and
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 4.
7 Press
to confirm.
8 Press
.
9 Select 0 (0: fan ON, 1: fan OFF (factory setting)).
10 Press
to confirm.
FTXTP-M and ATXTP-M units
1 Press
,
, and
2 Press
.
3 Select SU.
4 Press
to confirm.
simultaneously.
simultaneously.
simultaneously.