6.13.2 Regenerative power ride-through control (Deceleration
stop)
: Regenerative power ride-through control (Deceleration stop)
Function
1) Regenerative power ride-through control:
This function continues the operation of the motor by utilizing motor regenerative energy in the
event of momentary power failure.
2) Slowdown stop in the event of momentary power failure:
If a momentary power failure occurs during operation, the inverter stops forcibly. (Deceleration time
varies with control.) When operation is stopped, the message "" is displayed (alternately)
on the operation panel.
After the forced stop, the inverter remains static until you put off the operation command
momentarily.
[Parameter setting]
Title
6
Note 1: Even when this parameter is set, the particular load conditions may cause the motor to coast. In this
case, combine (auto-restart function) to restart quickly after recovery.
[When power is interrupted]
Input voltage
Output frequency
[If momentary power failure occurs]
VFNC3C ENGLISH MANUAL
Function
Regenerative power ride-through control
(Deceleration stop)
About 100ms
Input voltage
Output frequency
F-26
NOT SUBJECTED FOR RESALE
Adjustment range
0: Disabled
1: Automatic setting
2: Slowdown stop
* The time for which the operation of the motor can be
continued depends on the machine inertia and load
conditions. Before using this function, therefore,
perform verification tests.
Default setting
0