Download Print this page

Toshiba VF-NC3C Instruction Manual page 48

Advertisement

FOR REFERENCES ONLY
4.4
EASY key function
 : Registered parameters display selection

 : Easy setting mode parameter 1 to 24
-
• Function
It is possible to switch between standard mode and easy setting mode using the EASY key.
Up to 24 arbitrary parameters can be registered to easy setting mode.
[Parameter setting]
Title
Registered parameters

display selection
4
It is possible to switch between standard mode and easy setting mode using the EASY key.
The way parameters are read out and displayed varies according to the mode selected.
Easy setting mode
Allows pre-registration (easy setting mode parameters) of frequently changed parameters and reading of only
registered parameters (maximum of 24 types).
Standard setting mode
Standard setting mode in which all parameters are read out.
[How to read out parameters]
To enter the setting monitor mode, switch to the setting monitor mode using the EASY key, and then press the
MODE key.
Turn the setting dial to read the parameter.
The relation between the parameter and the mode selected is shown below.
 =
* When the power is turned on, the inverter is in standard mode. Press the EASY key to switch to easy setting
mode.
 =
* When the power is turned on, the inverter is in easy setting mode. Press the EASY key to switch to standard
mode.
 =
* Always in easy setting mode.
VFNC3C ENGLISH MANUAL
Function
0: Standard setting mode at power on
1: Easy setting mode at power on
2: Easy setting mode only
D-12
NOT SUBJECTED FOR RESALE
Adjustment range
Default setting
0

Advertisement

loading