FOR REFERENCES ONLY
 Table of output terminal functions 2
Function
Code
No.
40
RUN
Run/stop
41
RUNN
Inversion of run/stop
56
COT
Cumulative operation time alarm
57
COTN
Inversion of cumulative operation time alarm
60
FR
Forward/reverse run
61
FRN
Inversion of forward/reverse run
68
BR
Brake release
69
BRN
Inversion of brake release
78
COME
RS485 communication error
79
COMEN
Inversion of RS485 communication error
92
DATA
Designated data output
93
DATAN
Inversion of designated data output
128
LTA
Parts replacement alarm
129
LTAN
Inversion of parts replacement alarm
146
FLR
Fault signal (output also at a retry)
147
FLRN
Inversion of fault signal (output also at a
retry)
162
NSA
Number of starting alarm
163
NSAN
Inversion of number of starting alarm
254
AOFF
Always OFF
255
AON
Always ON
Note 1: As function No. 12, 13, 18, 19, 30 to 39, 42 to 55, 58, 59, 62 to 67, 70 to 77, 80 to 91, 94 to 127, 130 to 145 and 148
to 253 are "No function", output signal is always "OFF" at even number, output signal is always "ON" at odd number.
VFNC3C ENGLISH MANUAL
Function
ON: While operation frequency is output or DC braking is in
operation ()
OFF: Operation stopped
Inversion of RUN
ON: Cumulative operation time is  or more
OFF: The cumulative operation time is less than 
Inversion of COT
ON: Reverse run
OFF: Forward run
(The last status is held while motor operation is stopped)
Inversion of FR
ON: Brake exciting signal
OFF: Brake releasing signal
Inversion of BR
ON: Communication error occurred
OFF: Communication works
Inversion of COME
ON: bit0 of FA50 is ON
OFF: bit0 of FA50 is OFF
Inversion of DATA
ON: Any one of cooling fan, control board capacitor, or main
circuit capacitor reaches parts replacement time
OFF: Any one of cooling fan, control board capacitor, or main
circuit capacitor does not reach parts replacement time
Inversion of LTA
ON: While inverter is tripped or retried
OFF: While inverter is not tripped and not retried
Inversion of FLR
ON: Number of starting alarm is f648 or more
OFF: Number of starting alarm is less than f648
Inversion of NSA
Always OFF
Always ON
K-21
NOT SUBJECTED FOR RESALE
Action
Reference
3.2.1
6.16.11
3.2.1
6.18
6.19
6.19
6.16.14
6.12.3
6.24.16
7.2.2
7.2.2