FOR REFERENCES ONLY
(Continued)
Error code
Failure code
0012
EEPROM fault 1
0013
EEPROM fault 2
0014
EEPROM fault 3
0015
Main unit RAM fault
0016
Main unit ROM fault
0017
CPU fault 1
0018
Remote control error
001A
Current detector fault
*
001D
Low-current
operation
Trip
001E
Undervoltage trip
*
(main circuit)
0020
Over-torque trip
*
0022
Ground fault trip
0054
Auto-tuning error
0029
Inverter type error
0045
Over speed fault
0032
Brea in analog signal
*
cable
0033
CPU communications
error
0034
Excessive torque
boosted
0035
CPU fault 2
003A
CPU fault 3
* You can select a trip ON/OFF by parameters.
VFNC3C ENGLISH MANUAL
Problem
Possible causes
A data writing error occurs.
Power supply is cut off during
operation and data writing is aborted.
The error occurred when various data
was written.
A data reading error occurred.
The control RAM is defective.
The control ROM is defective.
The control CPU is defective.
The communication was broken off.
The current detector is defective.
The output current decreased to a low-
current detection level during operation.
The input voltage (in the main circuit) is
too low.
Over-torque reaches to a detection level
during operation.
A ground fault occurs in the output cable
or the motor.
The motor parameter , , ,
, are not set correctly.
The motor with the capacity of 2 classes
or less than the inverter is used.
The output cable is too thin.
The inverter is used for loads other than
those of three-phase induction motors.
The motor is rotating.
It may be a breakdown failure.
The input voltage fluctuates abnormally.
Over speed fault due to the overvoltage
limit operation.
The input signal from VI is equal to or less
than the setting.
A communications error occurs between
control CPUs.
The automatic torque boost parameter
setting is too high.
The motor has too small impedance.
The control CPU is defective.
The control CPU is defective.
M-3
NOT SUBJECTED FOR RESALE
Remedies
Turn off the inverter, then turn it again. If it
does not recover from the error, make a
service call.
Turn the power off temporarily and turn it
back on, and then try operation
again.
Write the data again. Make a service call
when it happening frequently.
Turn off the inverter, then turn it again. If it
does not recover from the error, make a
service call.
Make a service call.
Make a service call.
Make a service call.
Check the remote control device, cables,
etc.
Make a service call.
Enable (low-current detection).
Check the suitable detection level for the
system (, , ).
Make a service call if the setting is
correct.
Check the input voltage.
Enable (undervoltage trip
selection).
To take measures to momentary power
failure, set = or ,
Regenerative power ride-through control
f302 and Auto-restart control selection
f301.
Enable (over-torque trip
selection).
Check system error.
Check the cable and the motor for ground
faults.
Set the left column parameters correctly
as a motor name plate and make an auto-
tuning again.
Set the left column parameters correctly
as a motor name plate and make an auto-
tuning again.
Then set f400=1, when trip occurs.
Make an auto-tuning again after the
rotation of the motor stops.
Make a service call.
Check the input voltage.
Install an optional braking module.
Check the VI signal cable for breaks.
Also, check the input signal value or
setting of .
Make a service call.
Set a lower automatic torque boost
parameter setting.
Make an auto-tuning.
Make a service call.
Make a service call.
13