<Broadcast communication>
When sending an operation frequency command via a broadcast from the host computer
Host computer
*
INV No.00
: Split the cable among terminal blocks.
(1)
Send data from the host computer.
(2)
The inverters receive data from the host computer and the inverter number is checked.
(3)
When * is next to the position of an inverter number, it is judged a broadcast. The command is
decoded and processed.
(4)
To prevent data conflicts, only inverters where * is overwritten to 0 can reply with data to the host
computer.
(5)
As a result, all inverters are operating with the broadcast operation frequency command.
Note: Specify inverter numbers by group for group broadcasts.
(Function only for ASCII mode. For parity mode, see the Communications Function Instruction Manual.)
(Ex) When *1 is set, inverters 01, 11, 21, 31 to 91 can be broadcast to.
In this case, the inverter specified in 01 can reply.
6.22 Free notes
 : Free notes
 Function
To enable easier management and maintenance of the inverter, it is possible to enter the identification
number.
[Parameter setting]
Title
 Free notes
VFNC3C ENGLISH MANUAL
*
*
*
INV No.01
INV No.02
INV No.03
Function
0 - 65535
F-73