10.6 Output Terminal Function
 Table of output terminal functions 1
Function
Code
No.
0
LL
Frequency lower limit
1
LLN
Inversion of frequency lower limit
2
UL
Frequency upper limit
3
ULN
Inversion of frequency upper limit
4
LOW
Low-speed detection signal
5
LOWN
Inversion of low-speed detection signal
6
RCH
Output frequency attainment signal
(acceleration/deceleration completed)
7
RCHN
Inversion of output frequency attainment
signal
(inversion of acceleration/deceleration
completed)
8
RCHF
Set frequency attainment signal
9
RCHFN
Inversion of set frequency attainment signal
10
FL
Fault signal (trip output)
11
FLN
Inversion of fault signal (inversion of trip
output)
14
POC
Over-current pre-alarm
15
POCN
Inversion of over-current pre-alarm
16
POL
Overload detection pre-alarm
17
POLN
Inversion overload pre-alarm
20
POH
Overheat pre-alarm
21
POHN
Inversion of overheat pre-alarm
22
POP
Overvoltage pre-alarm
23
POPN
Inversion of overvoltage pre-alarm
11
24
MOFF
Power circuit undervoltage detection
25
MOFFN
Inversion of power circuit undervoltage
detection
26
UC
Small current detection
27
UCN
Inversion of small current detection
28
OT
Over-torque detection
29
OTN
Inversion of over-torque detection
VFNC3C ENGLISH MANUAL
Function
ON: Output frequency is more than 
OFF: Output frequency is or less
Inversion of LL
ON: Output frequency is or more
OFF: Output frequency is less than 
Inversion of UL
ON: Output frequency is  or more
OFF: Output frequency is less than 
Inversion of LOW
ON: Output frequency is within command frequency 

OFF: Output frequency is more than command frequency 

Inversion of RCHF
ON: Output frequency is within ±
OFF: Output frequency is more than  ±
Inversion of RCHF
ON: Inverter tripped
OFF: Inverter not tripped
Inversion of FL
ON: Output current is  or more
OFF: Output current is less than 
Inversion of POC
ON: 50% or more of calculated value of overload protection
level
OFF: Less than 50% of calculated value of overload
protection level
Inversion of POL
ON: Approx. 95C or more of IGBT element
OFF: Less than approx. 95C of IGBT element (90C or less
after detection is turned on)
Inversion of POH
ON: Overvoltage limit in operation
OFF: Overvoltage detection canceled
Inversion of POP
ON: Power circuit undervoltage (MOFF) detected
OFF: Undervoltage detection canceled
Inversion of MOFF
ON: After output current comes to  or less, value of
less than + for  set time
OFF: Output current is more than 
(+ or more after detection turns on)
Inversion of UC
ON: After torque comes to  or more, value of more
than - for  set time
OFF: Torque is less than 
(-or less after detection turns on)
Inversion of OT
K-20
NOT SUBJECTED FOR RESALE
Action
Reference
5.9
5.9
7.2.2
6.1.1
6.1.2
6.1.3
7.2.2
6.16.2
3.5
-
6.12.4
6.16.12
6.16.7
6.16.9