6.19 Adjustment parameters
6.19.1 Pulse train output for meters
 : Logic output/pulse train output selection (OUT)
 : Pulse train output function selection (OUT)
 : Maximum numbers of pulse train
 Function
Pulse trains can be sent out through the OUT output terminals.
To do so, it is necessary to select a pulse output mode and specify the number of pulses.
Ex.: When operations frequencies (0 to 60Hz) are put out by means of 0 to 600 pulses
=60.0, =1, =0, =0.60
[Parameter setting]
Title
6



Digital panel meter for reference
Type: K3MA-F (OMRON)
Connection terminal: OUT-E4, NO-E5
Note 1: When item of f676 reaches "Reference of max. value", the number of pulse train set by f677
are sent to output terminals (OUT)
Note 2: The pulse ON/OFF duty ratio is fixed at 50%.
Note 3: The minimum pulse output rate is 25pps. Keep in mind that no pulses can be put out at any rate
smaller than 25pps.
Note 4:  =  is the motor drive frequency.
VFNC3C ENGLISH MANUAL
Function
Logic output/pulse train
0: Logic output
output selection (OUT)
1: Pulse train output
0: Output frequency
1: Output current
2: Frequency reference
3: Input voltage (DC detection)
4: Output voltage (command value)
5 to11: -
12: Frequency setting value (after
compensation)
Pulse train output function
13: VI input value
selection (OUT)
14: -
15: Fixed output 1
(Output current: 100% equivalent)
16: Fixed output 2
(Output current: 50% equivalent)
17: Fixed output 3
(Other than the output current)
18: RS485 communication data
19-22: -
Maximum numbers of
0.50-1.60 (kpps)
pulse train
F-58
NOT SUBJECTED FOR RESALE
Reference
of maximum
Adjustment range
value of

185%
150%
150%
10 V/20 mA
185%
185%
100%
100.0%
Default
setting
0


-

-
0
-
0.80