Error code
Failure code

000B

000C

000D

000E

003E

0010
13

0011
(Continued overleaf)
VFNC3C ENGLISH MANUAL
Problem
Possible causes
 The deceleration time  is too short.
Overvoltage during
deceleration
(Regenerative energy is too large.)
 Overvoltage limit operation  is set
to , , .
  is set to . (Disabled).
 The input voltage fluctuates abnormally.
(1) The power supply has a capacity of
200kVA or more.
(2) A power factor improvement capacitor is
opened and closed.
(3) A system using a thyrister is connected
to the same power distribution line.
 The input voltage fluctuates abnormally.
Overvoltage during
constant-speed
(1) The power supply has a capacity of
operation
200kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyrister is connected
to the same power distribution line.
 The motor is in a regenerative state
because the load causes the motor to run
at a frequency higher than the inverter
output frequency.
 The acceleration time ACC is too short.
Inverter overload
 The DC braking amount is too large.
 The V/F setting is improper.
 A restart signal is input to the rotating
motor after a momentary stop, etc.
 The load is too large.
 The V/F setting is improper.
Motor overload
 The motor is locked up.
 Low-speed operation is performed
continuously.
 An excessive load is applied to the motor
during operation.
 The carrier frequency is high and load
Main module
overload
current has increased at low speeds
(mainly at 15Hz or less).
 The cooling fan does not rotate.
Overheat
 The ambient temperature is too high.
 The vent is blocked up.
 A heat generating device is installed close
to the inverter.
 During automatic operation or remote
Emergency stop
operation, a stop command is entered
from the operation panel or a remote
input device.
M-2
NOT SUBJECTED FOR RESALE
Remedies
 Increase the deceleration time .
 Decrease the overvoltage stall protection
level .
 Set  to , , .
 Insert a suitable input reactor.
 Insert a suitable input reactor.
 Install an optional brake resister.
(4004P and 4007P models cannot be used
brake resister.)
 Increase the acceleration time .
 Reduce the DC braking amount 
and the DC braking time .
 Check the V/F parameter setting.
 Use  (auto-restart) and 
(ride-through control).
 Use an inverter with a larger rating.
 Check the V/F parameter setting.
 Check the load (operated machine).
 Adjust  to the overload that the
motor can withstand during operation in a
low speed range.
 Raise the operation frequency.
 Reduce the load.
 Reduce the carrier frequency.
 When an operating motor is started up at
0Hz, use the auto-restart function.
 Set carrier frequency control mode
selection f316 to 1. (carrier frequency
with automatic reduction).
 The fan requires replacement if it does
not rotate during operation.
 Restart the operation by resetting the
inverter after it has cooled down enough.
 Restart the operation by resetting the
inverter after it has cooled down enough.
 Secure sufficient space around the
inverter.
 Do not place any heat generating device
near the inverter.
 Reset the inverter.
 If the emergency stop signal is input,
reset after releasing this signal.