Toshiba VF-NC3C Instruction Manual page 142

Advertisement

FOR REFERENCES ONLY
Title

Block write data 1
 Block write data 2
 Block read data 1
 Block read data 2
 Block read data 3
 Block read data 4
 Block read data 5
* Disabled ........... Indicates that the inverter will not be tripped even if a communication error occurs.
Trip ................... The inverter trips when a communication time-over occurs.
Alarm ................ When a communication time-over occurs, an alarm can be output from the output terminal.
VFNC3C ENGLISH MANUAL
Function
0: No selection
1: Command information
2: -
3: Frequency setting
4: Output data on the terminal
board
5: Analog output for
communication
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VI terminal board monitor
In this case a trip information  flashes on and off on the operation panel.
Output terminal function: 78 (RS485 communication error) or 79 (RS485 communication
error reverse)
F-69
NOT SUBJECTED FOR RESALE
Adjustment range
Default setting
0
0
0
0
0
0
0
6