☆ Setting acceleration/deceleration time (,) in conformance with mean load allows optimum
setting that conforms to further changes in load.
☆ Use this parameter after actually connecting the motor.
☆ When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or
deceleration time in time, and therefore may be tripped.
☆ Do not use  = when using a brake module (optional).
[Methods of setting automatic acceleration/deceleration]
Operation panel
action
MODE
5
☆ Assigning the forced detection command (function number 122, 123) to any logic input terminal, it can be
changed automatic detection on a mandatory.
5.3.2
Manually setting acceleration/deceleration time
Set acceleration time from 0.0 (Hz) operation frequency to maximum frequency  and deceleration time as
the time when operation frequency goes from maximum frequency  to 0.0 (Hz).
Output frequency (Hz)
[Parameter setting]
Title


Note: When the acceleration/deceleration time is set to 0.0 seconds, the inverter accelerates and decelerates
0.05 seconds.
LED display
Displays the operation frequency.

(When standard monitor display selection  is set to 
[Operation frequency])

The first basic parameter "" (history function) is displayed.

Turn the setting dial to the right to change the parameter to .
Parameter values can be read by pressing the center of the setting
dial.
Press the center of the setting dial to save the changed parameter.

 and the parameter are displayed alternately.

O


Function
Acceleration time 1
Deceleration time 1
E-6
Operation
  (Manual)
Time [sec]
Adjustment range
Default setting
0.0-3000 s
0.0-3000 s
E6581795
.
10.0
10.0