[Parameter setting]
Title

PID control waiting time

PID control

Proportional gain

Integral gain

Differential gain
PID forward/reverse characteristics

selection
1) External connection
2) Types of PID control interfaces
Set process amount input value (frequency setting) for when doing PID control.
Process amount input value (frequency setting)
Frequency setup mode selection: 
1: Setting dial 1 (press in center to save)
2: Setting dial 2 (save even if power is off)
3: RS485 communication
5: UP/DOWN from external logic input
Preset-speed operation (,  are all possible)
Note 1: Regarding setting value for : Terminal VI is used for a feed back signal, do not set 
(terminal VI).
VFNC3C ENGLISH MANUAL
Function
0-2400 [s]
0: Disabled, 1: Enabled
0.01-100.0
0.01-100.0
0.00-2.55
0: Forward
1: Reverse
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
(1) Panel setting
(1) Panel keypad setting
VI
(2) Internal preset-speed
setting
CC
Feedback signals (1)DC : 4~20mA (2)DC : 0~10V (3)DC : 0~5V
F-37
NOT SUBJECTED FOR RESALE
Adjustment range
Default setting
M
Pressure
transmitter
P
Feedback signal
External analog input
VI (DC: 4 - 20mA/
DC: 0 - 10V/
DC: 0 - 5V)
0
0
0.30
0.20
0.00
0
6