6.7
Operation frequency
6.7.1
Starting frequency
 : Starting frequency setting
 Function
The frequency set with  is put out as soon as operation is started.
Use the  parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title

6
6.7.2
Run/stop control with frequency setting signals
 : Operation starting frequency
 : Operation starting frequency hysteresis
 Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title


VFNC3C ENGLISH MANUAL
Function
Starting frequency setting
Output frequency (Hz)
Starting frequency 
0
Operation signal (F-CC)
Function
Operation starting frequency
Operation starting frequency hysteresis
Output frequency [Hz]
 
 + 
 -

0
A
B
F-18
NOT SUBJECTED FOR RESALE
Adjustment range
0.1-10.0 (Hz)
Time
ON
OFF
Adjustment range
0.0- (Hz)
0.0- (Hz)
When the frequency command signal
reaches the B point, the inverter
operates.
When decelerating, operation stops
when the frequency setting signal is less
than point A.
100% Frequency command value
Default setting
0.5
Default setting
0.0
0.0