ILC 1X1
Table 4-6
System variables of the control processor
System variable
COP_DIAG_STATUS_REG_RT_ERR
COP_DIAG_STATUS_REG_FAT_ERR
COP_DIAG_STATUS_REG_WARN
COP_DIAG_STATUS_REG_PON
COP_DIAG_STATUS_REG_FC_RUN
COP_DIAG_STATUS_REG_FC_STOP
COP_DIAG_STATUS_REG_FC_HALT
COP_DIAG_STATUS_REG_FC_LDG
COP_DIAG_STATUS_REG_FC_DBG
COP_DIAG_STATUS_REG_FC_RDO
COP_DIAG_PARAM_REG
COP_DIAG_PARAM_2_REG
The realtime clock of the ILC 131 ETH/XC and ILC 151 ETH/XC Inline controllers has no power storage. When
switching on the power supply, the realtime clock must be synchronized again. The SNTP function blocks from
the IT library are required for synchronization. The IT library can be downloaded at
ucts.
Table 4-7
System variables of the power storage and realtime clock
System variable
RTC_BATTERY_LOW
RTC_DATA_INVALID
84
PHOENIX CONTACT
4.7
Control processor
The system variables listed below show the states of the diagnostic status register on the
control processor of the Inline controller.
Type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
WORD
WORD
4.8
Power storage, realtime clock
Type
BOOL
BOOL
Meaning
A runtime error (out of realtime) has occurred on the control pro-
cessor.
A fatal error has occurred on the control processor. Division by
zero, for example, leads to a fatal error.
A warning has been issued on the control processor.
Power ON (COP): the control processor is ready to operate.
Runtime system RUN
Runtime system STOP
Runtime system HALT
Runtime system LOADING
Runtime system DEBUG
Runtime system READONLY
Diagnostic parameter register of the control processor
Extended diagnostic parameter register of the control proces-
sor
Meaning
Low capacity of the power storage for the realtime clock.
TRUE:
Power storage device is being charged.
FALSE:
Power storage device is fully charged.
The charging process is complete.
The realtime clock data is invalid.
phoenixcontact.net/prod-
8385_en_02