Assigning The Ip Address For The Controller; Dynamic Configuration Protocol (Dcp) - Phoenix Contact ILC 131 ETH Installing And Operating Information

Hide thumbs Also See for ILC 131 ETH:
Table of Contents

Advertisement

8385_en_02
3.3

Assigning the IP address for the controller

The procedure for assigning the IP address is essentially the same in PC Worx and
PC Worx Express for all Inline controllers described in this user manual.
By default, the Inline controller has no preset IP address. Initial setting of the IP address can
be carried out with the PC Worx/PC Worx Express software manually via the serial inter-
face, using the DCP protocol, or by means of a BootP server. The IP address can be
changed later with the PC Worx/PC Worx Express software via the serial connection, Ether-
net, or the DCP protocol.
3.3.1

Dynamic Configuration Protocol (DCP)

The Inline controllers support the DCP protocol from firmware version 4.20 or later and
from PC Worx version 6.30.767 or later (part of the AUTOMATIONWORX Software Suite
1.81 including AddOn V1).
The IP address is assigned via the DCP protocol in the PC Worx/PC Worx Express software
via the "Device Details" window:
Select the "IP Settings" tab.
Enter the IP address of the Inline controller.
Figure 3-2
DCP: setting the IP address
The "IP Assignment" tab is used for the actual IP address assignment with DCP.
Select the "IP assignment" tab.
After selecting the "IP Assignment" tab, the PROFINET network is searched for DCP de-
vices.
Click on "Assign IP" to start IP address assignment with DCP.
The Inline controller under PC Worx/PC Worx Express
45