Diagnostic Status Register; System Variables Of The Diagnostic Status Register - Phoenix Contact ILC 131 ETH Installing And Operating Information

Hide thumbs Also See for ILC 131 ETH:
Table of Contents

Advertisement

ILC 1X1
Table 4-2

System variables of the diagnostic status register

System variable
MASTER_DIAG_STATUS_REG_USER
MASTER_DIAG_STATUS_REG_PF
MASTER_DIAG_STATUS_REG_BUS
MASTER_DIAG_STATUS_REG_CTRL
MASTER_DIAG_STATUS_REG_DTC
MASTER_DIAG_STATUS_REG_RUN
MASTER_DIAG_STATUS_REG_ACT
MASTER_DIAG_STATUS_REG_RDY
MASTER_DIAG_STATUS_REG_BSA
MASTER_DIAG_STATUS_REG_SYSFAIL
MASTER_DIAG_STATUS_REG_RES
MASTER_DIAG_STATUS_REG_SYNCRES
MASTER_DIAG_STATUS_REG_DCR
MASTER_DIAG_STATUS_REG_WARN
MASTER_DIAG_STATUS_REG_QUAL
MASTER_DIAG_STATUS_REG_SSINFO
MASTER_DIAG_STATUS_REG_HI
MASTER_DIAG_STATUS_REG_LOW
80
PHOENIX CONTACT
4.3

Diagnostic status register

Information on the operating state of the Inline controller is stored in the diagnostic status
register. Every bit in the diagnostic status register is assigned a certain Inline controller
state.
The following system variables can be used to read the diagnostic status register informa-
tion.
Type
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BOOL
BYTE
BYTE
Meaning
User error/parameterization error
I/O error
Bus error
Error on Inline controller/hardware fault
Diagnostic routine is active
Data transmission is active
Selected configuration is ready to operate
Inline controller is ready to operate
Bus segment aborted
System failure
Standard function processed negatively
Synchronization error occurred
Faulty data cycles
Defined warning time exceeded
Defined error density exceeded
A message is present
Master diagnostic status register, high byte
Master diagnostic status register, low byte
8385_en_02