Tested successfully: use under extreme ambient
conditions
The Inline controllers (ILC 131 ETH/XC, ILC 151 ETH/XC) have been tested successfully
over 250 temperature change cycles according to IEC 61131-2 in the range from -40°C to
+70°C.
The following conditions were observed:
–
The Inline devices for all connecting cables were connected with a minimum conductor
cross section of 0.5 mm
–
The Inline controller was installed on a wall-mounted horizontal DIN rail.
–
Fans were used to ensure continuous movement of air in the control cabinet.
–
The Inline controller was not exposed to vibration or shock.
–
The Inline controller was operated with a maximum of 24.5 V (ensured by using elec-
tronically regulated power supply units).
+
T
2 K
max
+
T
3 K
min
3 h + 30 min
0 °C
Figure A-4
Temperature change cycle
Temperature in the control cabinet/ambient temperature
Cycle
WARNING:
The Inline controllers (ILC 131 ETH/XC, ILC 151 ETH/XC) are not approved for use in
safety technology.
Tested successfully: use under extreme ambient conditions
²
.
3 h + 30 min
+
(3 0,6) K/min
t 1
1
t 1