7�3�9�9� CO
Tariff 1 consumption emissions ratio
Tariff 2 consumption emissions ratio
Tariff 1 generation emissions ratio
Tariff 2 generation emissions ratio
They have 1 decimal place.
(11)
7�3�9�10� Cost of energy consumption and generation�
Cost per kWh of tariff 1 consumption
Cost per kWh of tariff 2 consumption
Cost per kWh of tariff 1 generation
Cost per kWh of tariff 2 generation
They have 1 decimal place.
(12)
7�3�9�11� Programming Digital Output T1
Note: The CVM-E3-MINI-xxx-WiEth models do not have a Digital Output, so the alarm only triggers
the activation of the ALARM / ENERGY PULSES LED.
Maximum value
Minimum value
Variable code
Connection delay
Hysteresis
Latch
Latch time
Disconnection delay
Contacts status
(18)
The latch time is the time in seconds when the alarm will be latched. After this time, if the alarm condition has cleared,
the disconnection delay is activated If a 0 is programmed, the alarm remains latched and can only be unlatched manually.
Kilowatts per impulse
Variable code
Pulse width
100
consumption and generation emissions�
2
Table 86: Modbus memory map: CO
Configuration variable
(11)
Table 87: Modbus memory map: Cost of energy consumption and generation�
Configuration variable
(12)
Table 88: Modbus memory map: Programming Digital Output T1 (Alarm)
Configuration variable
(13)
Table 89: Modbus memory map: Programming Digital Output T1 (pulses output)
Programming Digital Output : Pulses output
Configuration variable
consumption and generation emissions�
2
CO
emissions
2
Address
2724
2725
2728
2729
Cost per kWh
Address
272C
272D
2730
2731
Programming Digital Output : Alarm
Address
Valid data margin
2AF8-2AF9
depending on the variable
2AFA-2AFB
depending on the variable
Table 38 and Table 39
2AFC
2AFD
0 - 9999 seconds
2AFE
2AFF
2B02
0 - 600 seconds
0 - 9999 seconds
2B00
0 : Normally open
2B01
1: Normally closed
Address
Valid data margin
2B20-2B21
0.001 - 999.99 kWh
2AFC
2B22
30 - 500 ms
Valid data margin
0 - 1�9999
0 - 1�9999
0 - 1�9999
0 - 1�9999
Valid data margin
0 - 1�9999
0 - 1�9999
0 - 1�9999
0 - 1�9999
Default value
0 - 99 %
0 : No
1: Yes
Default value
1.00 kWh
Table 40
100 ms
CVM-E3-MINI
Default
value
0
0
0
0
Default
value
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Instruction Manual
Need help?
Do you have a question about the CVM-E3-MINI and is the answer not in the manual?