System Maintenance; System Power-Off; Routine Maintenance - Huawei iSitePower-M V100R002C00 User Manual

Hide thumbs Also See for iSitePower-M V100R002C00:
Table of Contents

Advertisement

iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)

10.1 System Power-Off

10.2 Routine Maintenance

10.3 Troubleshooting
10.4 Battery Storage and Recharge
10.5 Storage with Low SOC
10.1 System Power-Off
Precautions
Powering Off the System
Step 1 Switch off the upstream AC input circuit breaker for the iSitePower-M system.
Step 2 Set the DC SWITCH on the power module to OFF.
Step 3 Hold down the manual ON/OFF switch for 5s to shut down the battery module.
----End
10.2 Routine Maintenance
To ensure that the power system operates properly for a long term, you are
advised to perform routine maintenance as described in this chapter.
Issue 01 (2022-07-15)
10
After the system powers off, the remaining electricity and heat may still cause
electric shocks and body burns. Therefore, wear protective gloves 5 minutes
after the system is powered off before performing any operation. Maintain
the product after all indicators are off.
When an iSitePower system is running, turning off the DC SWITCH of the
product cannot completely power off the system. In this case, you cannot
perform maintenance operations on the product.
Copyright © Huawei Technologies Co., Ltd.

System Maintenance

10 System Maintenance
165

Advertisement

Table of Contents
loading

This manual is also suitable for:

Map05a1Mab05b1

Table of Contents