iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
iSitePower-M V100R002C00 User Manual
(MAP05A1, MAB05B1)
Table 7-2 (Optional) Cables in capacity expansion scenario
No.
1
2
7.2 Cables prepared by the customer
7.2.1 Solar-Only Scenario
Table 7-3 Cables in Single-node system (capacity expansion scenario)
No.
One End
1
PV input
ports
2
AC output
3
Ground
point
4
Ground
point
Issue 01 (2022-07-15)
Cable
Battery power cable
(bottom cascading
cables)
Battery signal cable
(bottom cascading
cables)
Other End
Type
DC switch
Common outdoor PV
cable in the industry
(customer
side)
PDB
Outdoor three-core copper
cable (L/N/PE)
(customer
side)
Ground bar
Outdoor single-core
copper cable
(customer
side)
Ground point
Outdoor single-core
on the
copper cable
module for
capacity
expansion
Copyright © Huawei Technologies Co., Ltd.
Type
Common outdoor PV cable in the industry
Outdoor shielded twisted pair cable
Recommended
Specifications
● Conductor cross-
sectional area: 4–6 mm
● Cable outer diameter:
5.5–9 mm
● Conductor cross-
sectional area: 4–6 mm
● Cable outer diameter:
13.7–16.9 mm
Main ground cable: 4–6
2
mm
(same as the cross-
sectional area of the AC
input power cable)
Main ground cable: 6 mm
7 Preparing Cables
2
2
2
63