8.1 System Power-Off

Precautions
Powering Off the System
Step 1 Set the upstream AC input circuit breaker for the iSitePower-M system to OFF.
Step 2 Set the DC SWITCH on the power module to OFF.
Step 3 Hold down the black start button for 5s to shut down the battery module.
----End

8.2 Routine Maintenance

To ensure that the power system operates properly for a long term, you are
advised to perform routine maintenance as described in this chapter.
Before cleaning the system, connecting cables, and checking the grounding
reliability, power off the system.
Issue 01 (2021-09-30)
After the system powers off, the remaining electricity and heat may still cause
electric shocks and body burns. Therefore, wear protective gloves 5 minutes
after the system is powered off before performing any operation. Maintain
the product after all indicators are off.
When an iSitePower system is running, turning off the DC SWITCH of the
product cannot completely power off the system. In this case, you cannot
perform maintenance operations on the product.
CA UTION