Operation; Indicators; Key Function Description - Smartgen HGM8151 User Manual

Genset parallel controller
Table of Contents

Advertisement

4

OPERATION

4.1

INDICATORS

Alarm Type
No Alarm
Warning
Trip Alarm
Shutdown Alarm
Trip and Stop Alarm
Status indicator: light on from crank disconnect to ETS and off during other periods.
Gens normal Indicator: light on when generator is normal; flashing when generator state is abnormal;
off when there is no generator power.
4.2

KEY FUNCTION DESCRIPTION

Icons
Stop
Start
Manual Mode
Auto Mode
Mute/Reset Alarm
Close
Open
Set/Confirm
Up/Increase
Down/Decrease
Left
HGM8151 Genset Parallel Controller User Manual
Table 4 Alarm Indicators
Indicator off
Slow flashing (1 time/s)
Slow flashing (1 time/s)
Fast flashing (5 times/s)
Fast flashing (5 times/s)
Table 5 Key Description
Keys
Stop running generator in Auto/Manual mode; Lamp test (press
at least 3 seconds); Reset alarm in stop mode; During stopping
process, press this button again to stop generator immediately.
Start genset in Manual mode.
Press this key and controller enters in Manual mode.
Press this key and controller enters in Auto mode.
Alarming sound off; If trip alarm occurs, pressing the button at
least 3 seconds can reset this alarm.
Close breaker in manual mode.
Open breaker in manual mode.
Enter setting interface.
1) Screen scroll;
2) Up cursor and increase value in setting menu.
1) Screen scroll;
2) Down cursor and decrease value in setting menu.
1) Screen scroll;
2) Left move cursor in setting menu.
Alarm Indicator
Description
Page 10 of 66