6.3
f
uses
Model
GFW 400
GFW 500
GFW 600
6.3.1
Fuse GG
The electric protection device called FUSE GG must be done in order to grant the protection against the electric cable short cirrcuit
(see EN60439-1, par. 7.5 "Short-circuit protection and short-circuit with stand strength" and 7.6 "Switching devices and components
installed in assemblies", otherwise the equivalent EN61439-1 paragraphs)
Size I t
"630A
310000A2s"
"1000A
970000A2s"
1000A
970000A
2
s
GEFRAN spa via Sebina, 74 - 25050 Provaglio d'Iseo (BS)
Tel. 03098881 - fax 0309839063 - Internet: http://www.gefran.com
ULTRA RAPID FUSES
Code Format
Model Code
"PC32UD69V630TF
FUS-630S
"PC33UD69V1000TF
FUS-1000
PC33UD69V1000TF
FUS-1000
Power Dissipated @ In
60 W
338213"
50 W
338160"
60 W
338160