374 Chapter 17 Hardware procedures

Installing a BIM

Prerequisites
Procedure steps
241-1501-240 5.2S2
Install a breaker interface module (BIM) to control the power supply to the
power interface modules (PIMs) and to the cooling unit or units.
CAUTION
Risk of equipment damage by mixing BIMs
You must never mix a 20-amp BIM (NT6C60PA) and a
25-amp (AP6C67PA) together to power the same shelf.
Mixing BIMs in a pair will damage the equipment.
You must be familiar with "Safety considerations and best practices"
(page 53).
You need a BIM with PEC AP6C67PA for a Passport 20000 or
NT6C60PA for a Passport 15000. The PEC of a replacement BIM must
match the PEC of the previous BIM. When adding a second switch to a
NEBS 2000 frame, you need a pair of BIMs matched with the same PEC
and matched to the switch hardware they will power. Refer to
241-1501-200 Passport 15000, 20000 Hardware Description for the safe
combinations of BIMs within a BIP.
A BIP can contain the BIMs for a second switch before the switch is
installed in the same NEBS 2000 frame. That is, the BIP may have been
shipped with the second pair already installed.
1
When adding a pair of BIMs to power a second switch, the 2 left-hand BIM
slots are likely to be covered by BIM filler plates (P0887704) at the front
of the BIP. When the filler plates are present, you must:
unfasten the 2 slotted captive screws of the cover of the BIM captive
screws as shown in the figure "Physical characteristics of a BIM in a
BIP" (page 377) and let the cover swing down
remove each BIM filler plate by unfastening the large slotted captive
screw at the front of the BIP
put the plates aside for re-use on another BIP