Chapter 8 Programming; Precautions For Programming - Mitsubishi Electric NZ2GF-CCB User Manual

Cc-link ie field network-cc-link bridge module
Table of Contents

Advertisement

CHAPTER 8
This chapter describes the programming of the bridge module.
The program of the bridge module is written to the CPU module of the master station.
8.1

Precautions for Programming

(1) Cyclic transmission program
For a cyclic transmission program, interlock the link special relay (SB) and the link special register (SW) of the
master/local module with the remote register (RWr) of the bridge module.
• Data link status (own station) (SB0049)
• Data link status (each station) (SW00B0 to SW00B7)
• CC-Link operating status (RWr4 to RWr5) ( Page 105, Appendix 1 (4))
• Data link status of other stations on CC-Link (RWr8 to RWrB) ( Page 106, Appendix 1 (5))
For the link special relay (SB) and link special register (SW) of CC-Link IE Field Network, refer to the following.
 User's manual for the master/local module used