List Of Remote I/O Signals - Mitsubishi Electric NZ2GF-CCB User Manual

Cc-link ie field network-cc-link bridge module
Table of Contents

Advertisement

3.5

List of Remote I/O Signals

The following table lists the remote I/O signal (RX/RY) assignment of the bridge module.
• Assignment example ( Page 29, Section 3.7)
(1) Remote input (RX)
RX n+k+1F
n: The start address assigned to the bridge module by the station number setting in CC-Link IE Field Network
m: The last station number in CC-Link
k: The start address assigned to the CC-Link remote input of the last connected station number in CC-Link
(2) Remote output (RY)
RY n+k+1F
n: The start address assigned to the bridge module by the station number setting in CC-Link IE Field Network
m: The last station number in CC-Link
k: The start address assigned to the CC-Link remote input of the last connected station number in CC-Link
26
Bridge module to master station (RX)
Address
RX n+0
H
RX n+1
H
RX n+1F
H
RX n+20
H
RX n+3F
H
RX n+k+0
H
H
Master station to bridge module (RY)
Address
RY n+0
H
RY n+1
H
RY n+1F
H
RY n+20
H
RY n+3F
H
RY n+k+0
H
H
Description
RX0 of CC-Link
RX1 of CC-Link
RX1F of CC-Link
RX20 of CC-Link
RX3F of CC-Link
RX k+0
of CC-Link
H
RX k+1F
of CC-Link
H
Description
RY0 of CC-Link
RY1 of CC-Link
RY1F of CC-Link
RY20 of CC-Link
RY3F of CC-Link
RY k+0
of CC-Link
H
RY k+1F
of CC-Link
H
RX0 of the station number 1
RX1 of the station number 1
RX1F of the station number 1
RX0 of the station number 2
RX1F of the station number 2
RX0 of the station number m
RX1F of the station number m
RY0 of the station number 1
RY1 of the station number 1
RY1F of the station number 1
RY0 of the station number 2
RY1F of the station number 2
RY0 of the station number m
RY1F of the station number m

Advertisement

Table of Contents
loading

Table of Contents