(2) Warning codes
Error code
Classification
(hexadecimal)
0201
H
0203
H
0204
H
0205
H
0601
H
0602
H
0603
H
0604
H
0605
H
0606
H
0607
H
Minor error
0608
H
0609
H
060A
H
060B
H
060C
H
060D
H
060E
H
84
Error
description
• The error is automatically corrected immediately after it has occurred.
However, the history of errors that have occurred before this error is lost.
Data read error
• Take noise reduction measures such as using a shielded cable for
(error history)
connection.
• If the same error occurs again, the module may be in failure. Please consult
your local Mitsubishi representative.
Station number
Reset the switch to the station number that was set when the module was
switch changing
powered on.
error
Momentary power
Check the power supply to the bridge module.
failure occurrence
Startup mode
Set the startup mode switch to PRM.
switch out of range
Write the parameters again using the parameter processing of slave station.
If the same error occurs, register the latest profile of the bridge module to the
Invalid parameter
engineering tool and write the parameters again.
If the same error occurs again, the hardware of the bridge module is in failure.
Please consult your local Mitsubishi representative.
In parameter processing of slave station, set "Station information" so that it
meets the following condition:
Station information
(16A)+(54B)2304
setting error
• A: Number of remote I/O stations
• B: Number of remote device stations
In parameter processing of slave station, set the parameters so that the
Remote device
number of stations in which "Station type" of "Station information" is set to the
station setting error
remote device station is 42 or less.
Invalid station
In parameter processing of slave station, specify only the station numbers set
specification error
in "Station number" of "Station information" as the error invalid stations.
In parameter processing of slave station, set the parameters so that the sum
Station number
of the number set in "Station number" and "Number of occupied stations" of
setting error
"Station information" is 64 or less.
Write the parameters again using the parameter processing of slave station.
If the same error occurs, register the latest profile of the bridge module to the
Invalid parameter
engineering tool and write the parameters again.
If the same error occurs again, the hardware of the bridge module is in failure.
Please consult your local Mitsubishi representative.
• In parameter processing of slave station, specify only the station numbers
set in "Station number" of "Station information" as the reserved stations.
Reserved station
• In parameter processing of slave station, check if all the station numbers
specification error
set in "Station number" of "Station information" are set as the reserved
stations.
Station number
In parameter processing of slave station, set the parameters so that there is
already in use error
no duplication in "Station number" of "Station information".
In parameter processing of slave station, any of "Total module connected",
No parameter input
"Retry count", "Automatic reconnection station count", or "Station information"
error
has not yet been written. Write the parameters.
Action