6.4.3

Wiring of a CC-Link dedicated cable

This section describes the wiring of the terminal block for CC-Link.
(1) Preparation before wiring
(a) Available cable
For the bridge module, use a Ver.1.10-compatible CC-Link dedicated cable.
If cables other than a Ver.1.10-compatible CC-Link dedicated cable are used, normal data transmission is not
guaranteed.
(b) Connection order
Cables do not need to be connected in order of station number.
(c) Terminating resistor to be used
Always connect included terminating resistors (110, 1/2W (brown, brown, brown)) to the modules at both
ends of the CC-Link system.
(2) Wiring method
(a) Wiring diagram
There are no restrictions on the connection location of the bridge module. (Cables do not need to be connected
in order of station number.)
DA
Terminating
resistor
DB
DG
SLD
FG
(b) Actual wiring
(Blue)
(Blue)
(White)
(White)
(Yellow)
(Yellow)
CC-Link dedicated cable
Terminating
resistor
CHAPTER 6 INSTALLATION AND WIRING
(Blue)
DA
(White)
DB
(Yellow)
DG
CC-Link dedicated cable
SLD
FG
(Yellow)
(White)
(Blue)
(Blue)
DA
Terminating
(White)
resistor
DB
(Yellow)
DG
SLD
FG
6