5. COMMUNICATlOtJS IN THE NOIPROTOCOL MODE
MELSEGA
5.1
Setting Switches on the
Computer
Link Module AJ71UC24
Set the setting switches on the AJ71 UC24 as illustrated below:
Station number
settlng
switches
\
x 1
@
8
1
Set the switches to
station number
0 .
\
\Transmission specifications setting switches
SW11
Maln channel setting
OFF
(RS-232C)
.
SW12
Data
bit
setting
OFF (7 MU)
SW13
OFF
sw14
Transmlssion speed settlng
OFF
(MOOBPS)
I
sw15
ON
ON (Enabled)
SW17
EvenlOdd w l t y
sottlng
ON
(Even)
SW18
Stop blt settlng
OFF (1 bit)
SW21
Sum check
enabledldlsabled
OFF (Dlsabled]
sw22
sw23
SW24
Unused
-
Wrlte durlng
RUN
enablWdlsabied
OFF (Dlsabled)
Computer llnk/MultMrop link
ON (Computer
seiectbn
Ilnk)
POINT1
When a module other than the
AJ71UC24 is used as computer link
module, data communications described hereinafter can be executed
by setting the corresponding switches as shown above.
-