5. EXTERNAL WIRING

5.1 CC-Link Dedicated Cable Wiring

This section explains how to connect the safety master module, safety
remote I/O module, standard remote I/O module and/or remote device
module with CC-Link dedicated cables.
(1) The cable connecting sequence is not related with the station No.
(2) Be sure to connect the "terminating resistors" compatible with the
cable type to the modules on both ends of the CC-Link Safety
system. Connect each terminating resistor between "DA" and "DB".
(3) In the CC-Link Safety system, the terminating resistor to be used is
different depending on the applied cable.
Version 1.10 compatible CC-Link dedicated cable
CC-Link dedicated cable (Ver.1.00)
CC-Link dedicated high-performance cable
* This resisters are provided with QS0J61BT12
(4) The safety master module can be connected to any location other
than both ends.
(5) Star topology is not allowed.
(6) A connection method is shown below.
L'illustration ci-dessous est un exemple de méthode de
raccordement.
Safety master module
(Blue)
DA
Terminating
resistor
(White)
DB
(Yellow)
DG
SLD
FG
Cable type
Remote module
CC-Link dedicated cable
110
(brown-brown-brown)
130
(brown-orange-brown)
DA
DB
DG
SLD
CC-Link dedicated cable
FG
9
Terminating resister
1/2 W *
1/2 W
Remote module
DA
Terminating
resistor
DB
DG
SLD
FG