Omron SYSMAC CS Series Operation Manual page 62

Analog i/o units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

CS1W-PTS02 Isolated-type Resistance Thermometer Input Unit
Direction
Word
Resistance
n + 1
00 to 15
Thermome-
ter Input Unit
to CPU Unit
n + 2
00 to 15
n + 3
00 to 15
n + 4
00 to 15
n + 5
00 to 15
n + 6
00 to 15
n + 7
00 to 15
n + 8
00 to 15
n + 9
00
01
02
03
04
05
06
07
08
09
10
11
Bit
Name
Input No. 1 process value
Input No. 2 process value
Input No. 3 process value
Input No. 4 process value
Input No. 1 rate-of-change value
Input No. 2 rate-of-change value
Input No. 3 rate-of-change value
Input No. 4 rate-of-change value
Input No. 1
Rate-of-change value
L (low limit) alarm
Rate-of-change value
H (high limit) alarm
Input No. 2
Rate-of-change value
L (low limit) alarm
Rate-of-change value
H (high limit) alarm
Input No. 3
Rate-of-change value
L (low limit) alarm
Rate-of-change value
H (high limit) alarm
Input No. 4
Rate-of-change value
L (low limit) alarm
Rate-of-change value
H (high limit) alarm
Input No. 1 input disconnection
Input No. 2 input disconnection
Input No. 3 input disconnection
Input No. 4 input disconnection
Data range
–32768 to 32767
The present process
(8000 to FFFF Hex,
value is stored
0000 to 7FFF Hex)
according to the scal-
ing set in the allocated
–32768 to 32767
words of the DM Area.
(8000 to FFFF Hex,
0000 to 7FFF Hex)
–32768 to 32767
(8000 to FFFF Hex,
0000 to 7FFF Hex)
–32768 to 32767
(8000 to FFFF Hex,
0000 to 7FFF Hex)
–32768 to 32767
The process value
(8000 to FFFF Hex,
rate of change is
0000 to 7FFF Hex)
stored according to
the scaling set in the
–32768 to 32767
allocated words of the
(8000 to FFFF Hex,
DM Area.
0000 to 7FFF Hex)
–32768 to 32767
(8000 to FFFF Hex,
0000 to 7FFF Hex)
–32768 to 32767
(8000 to FFFF Hex,
0000 to 7FFF Hex)
0, 1
0: Rate-of-change
value > Set value
1: Rate-of-change
value ≤ Set value
0, 1
0: Rate-of-change
value < Set value
1: Rate-of-change
value ≥ Set value
0, 1
Same as for input No.
1.
0, 1
0, 1
Same as for input No.
1.
0, 1
0, 1
Same as for input No.
1.
0, 1
0, 1
0: Normal
1: Disconnection
0, 1
Same as for input No.
1.
0, 1
Same as for input No.
1.
0, 1
Same as for input No.
1.
Section 2-2