CS1W-PTR02 Analog Input Unit
Specifications
Item
Model
Applicable PC
Unit classification
Mounting position
Maximum number of Units
Unit numbers
Areas for data
CIO Area words
exchange with
allocated for
CPU Unit
Special I/O
Units
DM Area words
allocated for
Special I/O
Units
Number of inputs
Input signal type
User-defined scaling in industrial
units
Data storage in the CIO Area
Accuracy
Temperature coefficient
Resolution
Input signal range
Input impedance
Response time
Conversion period
Maximum time to store data in
CPU Unit
Input error detection
Operation at input disconnection
Function
Inrush input
limit
Process value
alarm
Mean value
processing
(input filter)
CS1W-PTR02
CS Series
CS-series Special I/O Unit
CS-series CPU Rack or CS-series Expansion Rack (Cannot be mounted to C200H
Expansion I/O Rack or SYSMAC BUS Remote I/O Slave Rack.)
96 (within the allowable current consumption and power consumption range)
00 to 95 (Cannot duplicate Special I/O Unit numbers.)
10 words/Unit
Analog Input Unit to CPU Unit:
All process values, process value alarms (L, H)
100 words/Unit
CPU Unit to Analog Input Unit:
Input signal type, scaling of process value in industrial units, process value alarm set-
ting (L, H), inrush input upper limit, inrush input upper limit time, zero/span adjustment
value, etc.
8
Either 0 to 100 mV or –100 to 100 mV.
Scaling required for the above input sig-
nals. (Any minimum and maximum values
can be set.) (8 inputs set separately.)
The value derived from carrying out the
following processing in order of the pro-
cess value data is stored in four digits
hexadecimal (binary values) in the allo-
cated words in the CIO Area.
1) Mean value processing → 2) Scaling →
3) Zero/span adjustment → 4) Inrush input
limit → 5) Output limits
±0.2% of full scale
±0.015%/°C of full scale
1/4,096 of full scale
For 0 to 100 mV: –15 to 115%; for –100 to 100 mV: –7.5 to 107.5%
Balanced: 1 MΩ (typical); unbalanced: 20 kΩ (typical)
1.2 s (travel time from input 0% to 90%, for step input)
200 ms/8 inputs
Conversion period + one CPU Unit cycle
None.
Undefined.
When the process value is increased from 2% or less, the inrush input limit function
limits the increase for a set time. (It is available only for inputs of 0 to 100 mV.) This
function can be used to prevent sudden process value increases due to inrush cur-
rents caused by motor startup and so on.
Upper limit value: –32,000 to 32,000
Upper limit time: 0 to 100 s
Process value 2-point alarm (H, L), hysteresis, and ON-delay timer (0 to 60 s) are
available.
Calculates the moving average for the past four process values (every 200 ms), and
stores that value in the CIO Area as the process value.
Specifications
Input signal type and scaling to industrial
units are separate for each of the 8 inputs.
Note Input signal type and scaling to
industrial units are set in the DM
Area.
Example:
Input signal type: 0 to 100 mV; industrial
unit scaling: 0 to 500. DM Area settings
are as follows:
Input signal type: 0 (0000 Hex)
Industrial unit maximum value stored: 500
(01F4 Hex)
Industrial unit minimum value stored:
0 (0000 Hex)
Section 2-7
95