CS1W-PMV01 Isolated-type Analog Output Unit
System Configuration
Features
Model Information
Unit classification
CS-series Special I/O Unit CS1W-PMV01
112
CS1W-PMV01
• Outputs in either 4 to 20 mA or 1 to 5 V (set separately for each of the four
outputs) the analog output values set in the allocated words of the CPU
Unit's CIO Area.
• Answer input function.
Actual output signals of 4 to 20 mA or 1 to 5 V are checked by being read
again from the output circuit, and are stored in the allocated words in the
CIO Area. Mean value processing is also possible.
• Output disconnection detection function (current output only).
• Output high/low limit function.
• Rate-of-change limit function.
• Output hold function when CPU Unit errors occur.
When a CPU Unit fatal error (including FALS execution), or a CPU error in
the CPU Unit occurs, or all outputs are turned OFF with the Output OFF
Bit, this function can hold either a preset value or the analog output value
prior to the error.
• Zero/span adjustment capability during operation.
Model number
Outputs
4 max.
Control terminal
Control terminal
Four analog outputs (4 to 20 mA, 1 to 5 V)
Control terminal
Control terminal
4 to 20 mA, 1 to 5 V (separate for each of four outputs)
Section 2-9
Outputs