Omron SYSMAC CS Series Operation Manual page 46

Analog i/o units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

CS1W-PTS01-V1 Isolated-type Thermocouple Input Unit
Item
Input impedance
Input disconnection detection cur-
rent
Response time
Conversion period
Maximum time to store data in
CPU Unit
Disconnection detection
Function
Mean value pro-
cessing (input fil-
ter)
Process value
alarm
Rate-of-change
calculation
Rate-of-change
alarm
Isolation
Insulation resistance
Dielectric strength
External connections
Unit number settings
Indicators
Front panel connector
Alarm time for CPU Unit cycle
time
Current consumption
Dimensions
Weight
Standard accessories
20 kΩ min.
0.1 µA (typical)
1 s (travel time from input 0% to 90%, for step input)
150 ms/4 inputs
Conversion period + one CPU Unit cycle
Detects disconnections at each input and turns ON the Disconnection Detection Flag.
Hardware detection time: Approx. 5 s
The process value overrange direction for when a disconnection occurs can be speci-
fied. (High: 115% of set input range; low: –15% of set input range)
Calculates the moving average for the specified number of process values (1 to 16),
and stores that value in the CIO Area as the process value.
Process value 4-point alarm (HH, H, LL, L), alarm hysteresis, and ON-delay timer (0 to
60 s) are available.
Calculates the amount of change per comparison time interval (1 to 16 s).
Rate-of-change 2-point alarm (H, L), alarm hysteresis (shared with process value
alarm), and ON-delay timer (0 to 60 s, shared with process value alarm) are available.
Between temperature inputs and between input terminals and PC signals: Isolation by
transformer
20 MΩ (at 500 V DC) between inputs
Between inputs: 1,000 V AC, at 50/60 Hz, for 1 min, leakage current 10 mA max.
Terminal block (detachable)
Set by rotary switches on front panel, from 0 to 95.
Three LED indicators on front panel (for normal operation, errors detected at the Ther-
mocouple Input Unit, and errors related to the CPU Unit).
Sensor input connector terminal block (detachable)
0.3 ms
5 V DC at 150 mA max., 26 V DC at 150 mA max.
35 × 130 × 126 mm (W × H × D)
Note The height including the Backplane is 145 mm.
450 g max.