Omron SYSMAC CS Series Operation Manual page 118

Analog i/o units
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

CS1W-PPS01 Isolated-type Pulse Input Unit
Item
Dimensions
Weight
Standard accessories
DM Area Allocations
Input
Input
Input
No. 1
No. 2
No. 3
m
Setting Group 1 (continuously refreshed area): Parameters that are continuously refreshed during PC operation (regardless of the
CPU Unit's operation mode)
m + 2
m + 8
m + 14
m + 3
m + 9
m + 15
m + 4
m + 10
m + 16
m + 5
m + 11
m + 17
m + 6
m + 12
m + 18
m + 7
m + 13
m + 19
Setting Group 2 (initial settings area): Parameters that are transferred one time from the CPU Unit to the Pulse Input Unit if m is other
than 12345 when the PC is powered up or the Pulse Input Unit is restarted.
m + 26
m + 34
m + 42
m + 27
m + 35
m + 43
m + 28
m + 36
m + 44
m + 29
m + 37
m + 45
m + 30
m + 38
m + 46
35 × 130 × 126 mm (W × H × D)
Note The height including the Backplane is 145 mm.
450 g max.
None
m = D20000 + unit number × 100 (unit number: 0 to 95)
Input
Decimal
Hexadecimal
No. 4
12345, 0
3039 Hex
0000 Hex
m + 20
–32768 to
8000 to FFFF Hex,
32767
0000 to 7FFF Hex
m + 21
–32768 to
8000 to FFFF Hex,
32767
0000 to 7FFF Hex
m + 22
–32768 to
8000 to FFFF Hex,
32767
0000 to 7FFF Hex
m + 23
–32768 to
8000 to FFFF Hex,
32767
0000 to 7FFF Hex
m + 24
0 to 32000 0000 to 7D00 Hex
m + 25
–32000 to
8300 to FFFF Hex,
32000
0000 to 7D00 Hex
m + 50
1000 to
03E8 to 7D00 Hex
32000
m + 51
0 to 3
0000 to 0003 Hex
m + 52
1 to 16
0001 to 0010 Hex
m + 53
0 to 32000 0000 to 7D00 Hex
m + 54
---
Bit 00 to 03: 0 to 3
Hex
---
Bit 04 to 07: 0 to 4
Hex
---
Bit 08 to 15: 00 Hex 00 Hex
Specifications
Default
(See note
1.)
0000 Hex
Default block read command
Specifies the direction of data transfer at PC
powerup or Unit restarting for DM words m+2
to m+57.
• 12345 (3039 Hex): The default data at the
left is transferred from the Pulse Input Unit to
the CPU Unit. When the transfer is com-
pleted, the value will become 0000 Hex.
• Other than 12345 (such as 0000 Hex): The
data in the allocated words of DM Area is
transferred from the CPU Unit to the Pulse
Input Unit.
Instantaneous value alarm settings
4200
Instantaneous value HH (high high limit) alarm
(1068 Hex)
setting
(Set at instantaneous value scaling value.)
4000
Instantaneous value H (high limit) alarm setting
(0FA0 Hex)
(Set at instantaneous value scaling value.)
0
Instantaneous value L (low limit) alarm setting
(0000 Hex)
(Set at instantaneous value scaling value.)
–200
Instantaneous value LL (low low limit) alarm
(FF38 Hex)
setting
(Set at instantaneous value scaling value.)
Zero/span adjustment
10000
Gain for span adjustment
(2710 Hex)
(Set value x 0.0001)
0
Zero adjustment value
(0000 Hex)
(Set at instantaneous value scaling value.)
10000
Pulse weight
(2710 Hex)
Set value x 0.0001 (0.1 to 3.2)
The product of multiplying the actual number of
pulses input x the value set here is input as the
instantaneous value and accumulated value.
0
Accumulated value stepdown
(0000 Hex)
0: x1; 1: x0.1; 2: x0.01; 3: x0.001
The product of multiplying the actual number of
pulses input x the pulse weight x the stepdown
ratio set here is input as the accumulated
value.
1
Number of process values for calculating mov-
(0001 Hex)
ing average for mean value processing
Instantaneous value conversion function
1000
Instantaneous value when 100% input
(03E8 Hex)
Note Pulses/time unit multiplied by pulse
weight
0
Decimal point position (from right) for instanta-
(0 Hex)
neous value when 100% input
0
Instantaneous value time unit (matching con-
(0 Hex)
version period)
0: 1 s; 1: 3 s: 2: 10 s; 3: 30 s; 4: 60 s
Not used.
Section 2-8
Data contents
105