Features and Functions
Process value
Rate of change
(See note.)
Rate-of-change high
limit alarm output
Alarm Hysteresis
Alarm output
Alarm setting
6
Comparison time interval
set from 1 s to 16 s
Time
Rate-of-change high
limit alarm setting
Time
Time
Note The rate of change is calculated every second (and not just once during the
comparison time interval) so that even minute changes in the process value
are detected.
An hysteresis can be set for the process value (or instantaneous value) alarm
and the rate-of-change alarm. The operation is as shown in the following dia-
gram.
This function is supported by the following Units:
CS1W-PTS01-V1 Isolated-type Thermocouple Input Unit
CS1W-PTS02/PTS03 Isolated-type Resistance Thermometer Input Unit
CS1W-PTW01 Isolated-type 2-Wire Transmitter Input Unit
CS1W-PDC01 Isolated-type Analog Input Unit
CS1W-PTR01 Power Transducer Input Unit
CS1W-PTR02 Analog Input Unit (100 mV)
CS1W-PPS01 Isolated-type Pulse Input Unit
Process value
Process value (comparison time interval: 3 s)
Hysteresis
Section 1-2
Process value input
and rate of change
Time
Time