Error Processing

1-6
Error Processing
Errors Detected by the Analog I/O Unit
ERC LED
RUN LED
(red)
(green)
Lit
Lit
Not lit
Note
The following table shows the contents of the LED indicator displays on the
front panel of the Analog I/O Unit. The contents shown here are the same for
all models. For error processing specific to each Unit, refer to the explanations
for the individual Units.
Contents
Probable cause
Setting Group 1 (con-
The Analog I/O Unit
tinuously refreshed
started up and was
area) error (See note
operating properly,
1.)
but an out-of-range
setting was made in
Setting Group 1 in the
DM Area.
Setting Group 1 (See
An out-of-range set-
note 1.) or Setting
ting was made for
Group 2 (See note 2.)
either Setting Group 1
error
or Setting Group 2 in
the DM Area.
1. The following table shows the processing and results for Setting Group 1.
Processing
When an out-of-
range setting is
made in Setting
Group 1 during
operation
When the setting is
changed within the
allowable range
during operation
When the power is
turned ON or the
Unit is restarted
with an error still in
effect.
When the setting is
made within the
allowable range,
and the power is
turned ON or the
Unit is restarted
Unit operation
The Unit continues
operating with the
Setting Group 1 data
prior to the change.
The Unit will not start
up.
Result
LED indicators on
The Unit continues
ERC indicator is lit.
to operate with the
RUN indicator
Setting Group 1
remains lit.
data prior to the
change.
The Unit operates
ERC indicator is not
with the Setting
lit. RUN indicator
Group 1 data after
remains lit.
the change.
The Unit will not
ERC indicator is lit.
start up.
RUN indicator is not
lit.
The Unit starts up
ERC indicator is not
normally.
lit. RUN indicator is
lit.
Section 1-6
Remedy
Restore the set value
to within the allowable
range. (There is no
need to power up
again or to restart the
Unit.)
Restore the set value
to within the allowable
range, and then either
power up again or
restart the Unit.
Data range error
Unit
address stored in
DM Area
The lowest DM
address where the
out-of-range error
occurred is stored,
in four digits hexa-
decimal, as the off-
set value from m
(i.e., the number of
added words).
If there is no other
error, 0000 Hex is
stored. (If there is
another error, the
offset value for that
DM address is
stored.)
The lowest DM
address where the
out-of-range error
occurred is stored,
in four digits hexa-
decimal, as the off-
set value from m
(i.e., the number of
added words).
If there is no other
error, 0000 Hex is
stored. (If there is
another error, the
offset value for that
DM address is
stored.)
23